- Question #251Emergency, Life Safety and Security
You are designing an audible alarm notification system for an office environment with an ambient noise level of 55 dBA. What dBA level should the horn be set at?
audible alarmnotification appliancedBA levelfire alarm - Question #252Emergency, Life Safety and Security
You are designing a strobe visual notification system for a fire alarm system. You have a hallway that is 4.6 m (15 ft) wide and 100 m (328 ft) long. How many strobes should be pla...
visual notificationstrobe placementfire alarmhallway spacing - Question #253Information Transport Systems (ITS) Distribution
An outside plant (OSP) cable must be placed under a pipeline with two side by side pipe runs. The distance between the outside pipes is 6 m (20 ft). What is the length of the condu...
outside plantpipeline crossingconduit lengthunderground cable - Question #254Information Transport Systems (ITS) Distribution
All entrance conduits should be equipped with a plastic or nylon line with a MINIMUM test rating of _________ pulling tension.
entrance conduitpull linepulling tensionconduit installation - Question #255Information Transport Systems (ITS) Distribution
You are placing an entrance cable between two buildings connected by a conduit 205.3 m (588 ft) in length. What would be the MAXIMUM length of unlisted OSP cable that could be used...
OSP cableunlisted cableentrance facilityNEC compliance - Question #256Information Transport Systems (ITS) Distribution
To reduce the chance of an accidental dig-up, plastic warning tape should be placed a MINIMUM of _________ below grade, but high enough above cables to allow detection before cable...
warning tapedirect burialunderground cableburial marking - Question #257Information Transport Systems (ITS) Distribution
What is the MINIMUM number of outside building terminal pedestals required to serve a single story office, or office warehouse structure that has ten 18.3 m x 24 m (60 ft x 80 ft)...
terminal pedestalOSPbuilding entranceservice distribution - Question #258Bonding, Grounding and Electrical Protection
What is the horizontal separation, in well tamped earth, required between power and direct buried telecommunications facilities sharing the same trench?
power separationshared trenchdirect burialelectrical separation - Question #259General Cable and Media
The MOST common medium used to provide service to the access point (AP) is ________ cable.
wireless access pointbalanced twisted paircable selectionhorizontal cabling - Question #260Information Transport Systems (ITS) Distribution
Which one of the following is NOT an advantage of direct-buried cable?
direct burialOSP installationcable methodsunderground cable - Question #261Information Transport Systems (ITS) Distribution
You have determined that your underground cable design requires three maintenance holes (MHs). One is 4.3 m (14 ft), one is 6 m (20 ft), and one is 6.7 m (22 ft) in length. How man...
maintenance holeMH coversunderground distributionhandhole - Question #262ITS Spaces
The information technology system (ITS) designer should design conduits entering a building from ceiling height to terminate ________ below the finished ceiling.
entrance conduitceiling terminationconduit routingbuilding entrance - Question #263ITS Spaces
Buildings larger than ________ must contain a dedicated room for the termination of entrance facilities.
entrance roomtelecommunications roombuilding size thresholdITS spaces - Question #264Information Transport Systems (ITS) Distribution
What is the MINIMUM vertical separation between the top rail of a railroad track and telecommunications facilities placed beneath the track?
railroad crossingvertical separationunderground clearanceOSP installation - Question #265Information Transport Systems (ITS) Distribution
Aerial entrances to small buildings should be limited to ________ cable pair or less.
aerial entrancecable pairssmall building entranceOSP aerial - Question #266ITS Spaces
The information technology system (ITS) designer should design conduits entering a building from below grade point to extend ________ above finished floor (AFF).
entrance conduitfloor heightbelow gradeconduit termination - Question #267Information Transport Systems (ITS) Distribution
You have the responsibility of designing a railroad track crossing for an outside plant OSP cable. There are three separate railroad tracks to be crossed. The measurement between t...
railroad crossingconduit lengthOSP designrigid steel conduit - Question #268Information Transport Systems (ITS) Distribution
When selecting poles for aerial telecommunications facilities, which of the following is the class number for the strongest rated pole?
utility polepole classaerial cablepole strength rating - Question #269Information Transport Systems (ITS) Distribution
What is the MINIMUM cover for underground conduit?
underground conduitminimum coverburial depthconduit installation - Question #270Information Transport Systems (ITS) Distribution
BICSI recommends that any trench ________ or more deep must be shored to prevent cave in.
trench safetyshoringunderground installationentrance facilities - Question #271Information Transport Systems (ITS) Distribution
When a building is not on the property line, the building owner should provide a MINIMUM of ________ conduits from a point inside the building, to the property line or easement for...
entrance facilitiesconduit countproperty lineunderground entrance - Question #272Information Transport Systems (ITS) Distribution
The MAXIMUM span length for an aerial entrance, from the last pole to the building, must NOT exceed:
aerial entrancespan lengthdrop wireentrance facilities - Question #273Information Transport Systems (ITS) Distribution
Vertical conduit masts (with approved service heads) are limited to drop-wire attachments of up to ________ lines.
conduit mastdrop wireaerial entranceline limits - Question #274General Cable and Media
What warning tape color has the Common Ground Alliance (CGA) adopted for telecommunications and CATV cables?
warning tapeCGAburied cable markingtelecommunications - Question #275Information Transport Systems (ITS) Distribution
Which one of the following is NOT an advantage of underground conduit?
underground conduitcost analysisinstallation advantagesentrance facilities - Question #276Information Transport Systems (ITS) Distribution
When installing underground entrances, no more than ________ 90-degree bends should be included between pulling points.
underground entranceconduit bendspulling pointsinstallation limits - Question #277Emergency, Life Safety and Security
Within a data center, how many concentric layers are considered necessary to provide effective security?
data center securityconcentric layersphysical securityaccess control - Question #278Emergency, Life Safety and Security
If you are working on a physical security plan for a data center and focusing on building and access control, what layer of the plan would this relate to?
data center securitysecurity layersbuilding access controlphysical security - Question #279Design, Implementation, and Management
What type of redundancy provides two additional units, modules, paths, or systems in addition to the MINIMUM required to satisfy the base requirement.
redundancyN+2fault tolerancedata center design - Question #280ITS Spaces
It is important to keep all underfloor cabling systems very neat and orderly. Cabling systems must be managed to ensure that air flow is not impeded by the height or volume of unde...
underfloor cablingairflow managementhot aisle cold aisledata center - Question #281ITS Spaces
Within a data center, if you have dual path connectivity between the primary entrance room and secondary entrance room, in addition to dual connectivity between these two rooms and...
data center tiersdual path connectivityTier IVdistribution areas - Question #282Emergency, Life Safety and Security
You have been asked to spec the physical security requirements related to the protection of assets for a new data center. The most common potential for damage categories you have c...
asset protectionenvironmental hazardsdata center securityphysical security categories - Question #283Design, Implementation, and Management
Within a data center, if you have a system which includes one extra unit, in addition to the minimum required to satisfy the base need, and where the failure of this unit will NOT...
redundancyN+1fault tolerancedata center design - Question #284Design, Implementation, and Management
What type of redundancy provides two complete units, modules, paths or systems for every one required for a base system.
redundancy2Nmirrored systemsdata center design - Question #285ITS Spaces
What is the MAXIMUM horizontal cable length permitted for centralized optical fiber cabling from the MDA within a data center?
centralized optical fiberMDAhorizontal cabling distancedata center - Question #286ITS Spaces
You are designing a cabling containment system installed overhead in a new data center. The main or prime purpose of the system will be to manage fiber optic cabling between cabine...
cable trayfiber optic containmentoverhead cablingsolid bottom tray - Question #287ITS Spaces
If you have a data center where the entire infrastructure must be completely shutdown on an annual basis to perform preventative maintenance and repair work, what tier level would...
data center tiersTier Ipreventive maintenancesystem availability - Question #288ITS Spaces
What does ANSI/TIA 942 recommend as the MINIMUM height for overhead cable tray above finished floor within a data center?
overhead cable trayANSI/TIA 942minimum heightdata center - Question #289ITS Spaces
If you have a 30 cm (12 in) wide data tray, what does ANSI/TIA 569-B recommend be the maximum pathway fill cross sectional area assuming a MAXIMUM pathway depth of 15 cm (6 in)?
pathway fillcable tray sizingANSI/TIA 569-Bcross sectional area - Question #290ITS Spaces
You are renovating telecommunication rooms that support an acute care facility that has 10,000 sq ft floors. The facility will be adding 15,000 sq ft to each of the floors. What is...
TR sizingacute care facilityfloor space expansionhealthcare - Question #291Emergency, Life Safety and Security
You are designing a nurse call system for a health care facility. The system will have emergency call switches. What is the first step you should take in designing the nurse call s...
nurse call systemrisk assessmentsystem designhealthcare - Question #292ITS Spaces
How much area of wall space is needed in the telecommunications room (TR) to support a nurse call system?
TR wall spacenurse call systemtelecommunications roomhealthcare - Question #293Emergency, Life Safety and Security
Which of the following is an alarm management output system?
alarm managementnurse call outputwireless telephonehealthcare systems - Question #294Emergency, Life Safety and Security
Which of the following is used to create an electronic signal that can be sent to the central nurse call equipment?
initiation devicenurse call systemelectronic signalcall equipment - Question #295Emergency, Life Safety and Security
You are designing a nurse call system for an assisted care facility. What type of nurse call system would best suit the needs for the facility?
nurse call systemassisted caretone/visual systemsystem selection - Question #296Special Applications
The ________ system is an application used for storing and viewing captured digital radiology image files.
PACSdigital radiologyhealthcare ITimage storage - Question #297Special Applications
You are designing an interactive patient television system (IPTS) that will provide internet, nurse call and LCD television services. From the following, which medium will NOT supp...
IPTSbackbone cabling mediabalanced twisted pairhealthcare multimedia - Question #298Special Applications
In new construction, what is the percentage of pay phones that must be equipped with volume controls?
ADApay phonesvolume controlsaccessibility requirements - Question #299Bonding, Grounding and Electrical Protection
Coupling with electrical circuits can create inductive interference to telecommunications facilities. Which of the following can decrease the coupling effect?
inductive interferenceEMI couplingelectrical separationexposure length - Question #300Special Applications
In this future marina layout, assuming that there are fewer than 10 slips being cabled, what would be the pre-cabling guideline to follow for terminal A?
marina cablingpre-cablingboat slipsdistribution terminal